Protective relays safeguard the most expensive equipment in the power system. The performance of these ralays needs to be checked / verified during commissioning and at periodic intervals. To check these ralays the protection engineer needs a reliable tool -A relay test set that incorporates State of the art hardware suitable for the field working conditions easy to operate, flexible and powerful software. With close interaction with relay manufacturers, Protection engineers and our expertise in designing and manufacturing relay test sets based on DSP technology, Tesient has launched a new, state of the art platform of relay test sets MP3000A. It can cater to most of the demanding applications in testing different types of modern relays.
Features:
| Number of Outputs | 4 |
|---|---|
| Voltage Ranges | AC (L-N): 4 × 0–300 V AC (L-L): 2 × 0–600 V DC (L-N): 4 × 0–±424 V DC (L-L): 2 × 0–±848 V |
| Output Power | AC (L-N): 4 × 100 VA typ. (>130 V), 4 × 75 VA guar. (>100 V) AC (L-L): 2 × 200 VA typ. (>260 V), 2 × 150 VA guar. (>200 V) DC (L-N): 4 × 70 W (>100 V) |
| Accuracy | Error < 0.15% rd. + 0.02% rg. (Guaranteed) Error < 0.1% rd. + 0.01% rg. (Typical) |
| Resolution | 10 mV (for 300 Vac) |
| Step Response Time | <100 µs at <75 V |
| Distortion (THD) | <0.05% typ., <0.1% guar. (at >5 V) |
| Frequency–Amplitude Characteristic | <0.5% at ≤450 Hz, <1% at ≤1000 Hz |
| Output Time | Continuous |
| Operation Indication | LED indication on front panel |
| Number of Outputs | 6 |
|---|---|
| Current Ranges | AC (L-N): 6 × 0–30 A 1-phase AC (6L-N): 1 × 0–180 A 3-phase AC (2L-N): 3 × 0–60 A DC (L-N): 6 × 0–±20 A DC (6L-N): 1 × 0–±120 A |
| Output Power | 6-phase AC (L-N): 6 × 450 VA typ., 6 × 400 VA guar. (30 A) 3-phase AC (2L-N): 3 × 800 VA typ., 3 × 700 VA guar. (60 A) 1-phase AC (6L-N): 1 × 1200 VA typ., 1 × 1000 VA guar. (180 A) DC (L-N): 6 × 250 W typ., 6 × 200 W guar. (20 A) DC (6L-N): 1 × 1200 W typ., 1 × 1000 W guar. (120 A) |
| Max Compliance Voltage (L-N) | 21 Vpk |
| Accuracy | Error < 0.1% rd. + 0.05% rg. (Guaranteed, 0–30 A) Error < 0.1% rd. + 0.02% rg. (Typical, 0–30 A) |
| Resolution | 1 mA |
| Step Response Time | <100 µs (Resistive load) |
| Distortion (THD) | <0.06% typ., <0.1% guar. |
| Frequency–Amplitude Characteristic | <0.5% at ≤450 Hz, <1% at ≤1000 Hz |
| Output Time | >15 seconds at 30 A |
| Operation Indication | LED indication on front panel |
| Frequency – Sine Signal Range | DC, 0.001 Hz – 1000 Hz |
|---|---|
| Transient Signal Range | DC – 5 kHz |
| Frequency Accuracy / Drift | ±1 ppm |
| Frequency Resolution | 0.001 Hz |
| Phase Angle Range | 0 – ±360° |
| Phase Angle Accuracy | <0.05° typ., <0.1° guar. (50 / 60 Hz) |
| Phase Angle Resolution | ±0.005° |
| Synchronization Time (I & V) | <20 µs |
| Voltage Range | 24 – 300 V |
|---|---|
| Maximum Current | 1 A |
| Maximum Power | 100 W |
| Accuracy | <0.2% rg. typ., <0.5% rg. guar. |
| Nominal Supply Voltage | 110 – 240 Vac, Single Phase |
|---|---|
| Permissible Supply Voltage | 90 – 260 Vac |
| Nominal Frequency | 50 / 60 Hz |
| Permissible Frequency | 45 – 65 Hz |
| Maximum Current | 10 A |
| Number of Inputs | 8 (4 Auto-detect, 4 Polarity-dependent) |
|---|---|
| Input Characteristics (1–4) | Auto-detect (White) 0 – 250 Vdc / Vac peak threshold or potential-free |
| Input Characteristics (5–8) | Potential-free or 0 – 250 Vdc (Polarity dependent) Red = Positive, Black = Negative |
| Sample Rate | 50 kHz |
| Time Resolution | 20 µs |
| Maximum Measuring Time | Infinite |
| Debounce / Deglitch Time | 0 – 25 ms |
| Counting Function | <5 kHz (Pulse width >100 µs) |
| Galvanic Isolation | 8 channels, galvanically isolated |
| Number of Outputs | 4 |
|---|---|
| Type | Potential-free relay contacts, software controlled |
| Break Capacity (AC) | 250 Vac / 5 A / 1250 VA |
| Break Capacity (DC) | 30 Vdc / 5 A / 150 W |
| Manufacture By | Tesient Instrument Co., Ltd |
| Origin | China |