Field Portable Reference Standard Meter is a cutting-edge device designed for high-precision calibration of electrical systems in the field. It measures essential parameters like voltage, current, power, and frequency with utmost accuracy, ensuring reliable testing and calibration of other equipment. Its lightweight, rugged construction makes it perfect for on-site calibration, even in harsh environmental conditions. With its user-friendly interface, operators can easily obtain reference-standard accuracy while on the go. Compact Field Portable Reference Standard Meter designed for electrical measurement export needs, provided at competitive pricing by Myriad Industrial Solutions LLP for diverse industrial sectors.
Applications: Ideal for electrical engineers in power plants, substation maintenance, and on-site electrical installations.
Standard Meter Features:
| Measured Parameters (34 parameters in total) |
Measurement Ranges | Intrinsic Measurement Error | |
|---|---|---|---|
| Accuracy Class 0.02 | Accuracy Class 0.05 | ||
| RMS of AC Voltage | 0.1 to 960 V | ±0.01 % | ±0.02 % |
| RMS of AC Current | 5 mA to 120 A | ±0.01 % | ±0.02 % |
| Phase Angle (Voltage Harmonics) | 0° to 360° | Absolute: ±0.01° | |
| Active Power | 0.01Un to 1.5Un | ±0.015 % | ±0.05 % |
| Reactive Power | 0.05Un…1.5Un | ±0.03 % | ±0.05 % |
| Power Factor | -1.0 to +1.0 | Absolute: ±0.001 | |
| AC Frequency | 40 to 70 Hz | ±0.001 Hz | ±0.003 Hz |
| Total Harmonic Distortion | 0 to 49.9 % | Absolute: ±0.003 % | |
| Interharmonics | 0 to 49.9 % | Relative: ±0.6 % | |
| CT / PT Ratio Error | 0.2 to 20 % | Absolute: ±0.005 % | |
| Flicker Short-Term Severity | 0.25 to 10 | Relative: 5.0 % | |
| Measured Parameters (Optional) | |||
| DC Voltage | 0.1 to 960 V | ±0.01 % | ±0.02 % |
| DC Current | 5 mA to 120 A | ±0.01 % | ±0.02 % |
| DC Power | 0.01Pn to 2.55Pn | ±0.03 % | ±0.04 % |
| Input | Output |
|---|---|
| 5 … 15 V | 5 V |
| 36 kHz | 18 kHz |
| > 14 µs | 10 ± 2 µs |
| 999 999 imp / (kW·h) | C = 144 · 10⁸ / (INOM · UNOM) imp / (W·h) |
| Operating Temperature | 10 to 30 °C |
|---|---|
| Relative Humidity | 80 % (20 °C) |
| Atmospheric Pressure | 84 to 106.7 kPa |
| Parameter | Value |
|---|---|
| Mains Supply | 100 … 264 V, (50 ± 5) Hz |
| Power Consumption from Mains | 100 VA or less |
| Dimensions (L × W × H) – Stationary – Portable |
Maximum 485 × 450 × 140 mm 480 × 380 × 200 mm |
| Weight – Stationary – Portable |
Maximum 8 kg 10 kg |